Steel Building Insulation: What the Energy Code Requires, Zone by Zone

Pre-engineered steel building frame with purlins and the first roof panels installed on a concrete slab

Steel building insulation must meet a U-factor set by the adopted energy code: in climate zone 4, ASHRAE 90.1-2022 caps a conditioned metal roof at U-0.037, while one R-19 blanket on a through-fastened roof rates U-0.151.

Key takeaways

  • ASHRAE 90.1-2022 limits a conditioned metal building roof to U-0.041 in climate zones 0 to 3, U-0.037 in zones 4 and 5, U-0.031 in zone 6, U-0.029 in zone 7 and U-0.026 in zone 8 (Owens Corning compliance guide, Pub. 10015581-J, September 2026).
  • A single R-19 blanket draped over purlins under a through-fastened roof rates U-0.151 in 90.1-2022 Appendix A, about 4.1 times the zone 4 limit; a liner system with R-19 + R-11 and R-3 thermal blocks rates U-0.037 and passes (Owens Corning, 2026).
  • The 2024 IECC, Section C401.2, lets a commercial building comply through ANSI/ASHRAE/IES 90.1 instead of the IECC chapter (City of Phoenix 2024 IECC amendments, 2025), and North Carolina’s fire marshal rules that the chosen path covers the whole building, not just the envelope (NC OSFM, 2020).
  • The NAIMA 202 standard (2021 edition) requires a three-roll average of at least 103% of the nominal R-value, but Section 1.4 states that rated R-values exclude facings, air films and compression at the framing.
  • The MBMA Condensation Fact Sheet reports NAIMA’s recommendation of a facing rated at 0.10 perm or less, calls plain white vinyl (1.0 to 1.3 perm) not an effective vapor retarder, and asks for less than 0.05 perm in high-humidity buildings.

Which energy code sets steel building insulation levels?

A steel building’s insulation level comes from the commercial energy code your state or city enforces: the International Energy Conservation Code (IECC) or ANSI/ASHRAE/IES Standard 90.1. Both use the same U.S. climate zone map and both offer a prescriptive R-value path and a maximum U-factor path, according to the Owens Corning guide Pub. 10015581-J (September 2026).

A U-factor is the rate heat passes through the whole roof or wall, including where the blanket is squeezed flat over each purlin. Lower is better, and 1 divided by U gives the effective R-value of the assembly: U-0.037 is about R-27 for the whole assembly, while a single R-19 roll over purlins rates U-0.151, about R-6.6.

Under the 2024 IECC, a commercial building follows one of two paths: the IECC’s own prescriptive or performance rules, or ASHRAE 90.1 (Sections C401.2.1 and C401.2.2, as quoted in the City of Phoenix amendments under Ordinance G-7397, effective August 1, 2025). The North Carolina Office of State Fire Marshal ruled on January 13, 2020 that a project taking the 90.1 path follows it for the envelope and the mechanical, lighting and water heating trades alike.

Which edition applies depends on the state. As of October 7, 2026, 10 states enforce a code based on 90.1-2022 or the 2024 IECC, 15 use 90.1-2019 or the 2021 IECC, and 10 have no statewide commercial energy code, based on the U.S. Department of Energy state-level commercial code data dated September 15, 2026. Our state-by-state registry lists the edition, effective date and source for each state in the commercial energy code by state report.

Code edition in force (90.1 / IECC)Jurisdictions, Oct 202690.1 zone 4 conditioned metal roof, max UIECC zone 4 metal roof, max USource
90.1-2022 / 2024 IECC100.0370.035 (2024 development text)DOE BECP 2026; Owens Corning 2026; ICC CED1-100-22
90.1-2019 / 2021 IECC150.0370.035DOE BECP 2026; Owens Corning 2026
90.1-2016 / 2018 IECC40.0370.035DOE BECP 2026; Owens Corning 2026
90.1-2013 / 2015 IECC60.0370.035DOE BECP 2026; Owens Corning 2026
90.1-2010 / 2012 IECC20.0550.035DOE BECP 2026; Owens Corning 2026
90.1-2007 / 2009 IECC3Not in source0.055DOE BECP 2026; Owens Corning 2026
90.1-2004 / 2006 IECC1Not in sourceNot in sourceDOE BECP 2026
No statewide code10Local codeLocal codeDOE BECP 2026

The table shows why the edition matters less than the path for most owners. For climate zones 2 to 7, the metal building roof U-factor is identical in every 90.1 edition from 2013 to 2022 and every IECC edition from 2012 to 2021, per the Owens Corning tables, so in those zones the 35 jurisdictions on 90.1-2013 or the 2015 IECC and newer apply the same metal roof targets as the newest editions. The climate zone itself comes from IECC Table C301.1, which lists zones by county; the map was redrawn for 90.1-2016 and the 2018 IECC, which added zone 0.

What U-factor does a metal building roof and wall need in each climate zone?

A conditioned metal building needs a roof U-factor of 0.026 to 0.041 and a wall U-factor of 0.039 to 0.094 under ASHRAE 90.1-2022, depending on the climate zone. The 2021 IECC is stricter in zones 0 to 3, at roof U-0.035 and wall U-0.079. Semiheated spaces get far looser limits: a zone 4 semiheated roof may reach U-0.082.

Climate zone90.1-2022 roof, conditioned (max U)90.1-2022 roof, prescriptive R90.1-2022 roof, semiheated (max U)2021 IECC roof (max U)90.1-2022 wall, conditioned (max U)2021 IECC wall (max U)Source
0 and 10.041R-10 + R-19 FC0.1150.0350.0940.079Owens Corning 10015581-J (Sept 2026)
2 and 30.041R-10 + R-19 FC0.0960.0350.0940.079Owens Corning 10015581-J (Sept 2026)
40.037R-19 + R-11 LS or R-25 + R-8 LS0.0820.0350.0600.052Owens Corning 10015581-J (Sept 2026)
50.037R-19 + R-11 LS or R-25 + R-8 LS0.0820.0350.0500.050Owens Corning 10015581-J (Sept 2026)
60.031R-25 + R-11 LS0.0600.0310.0500.050Owens Corning 10015581-J (Sept 2026)
70.029R-30 + R-11 LS0.0370.0290.0440.044Owens Corning 10015581-J (Sept 2026)
80.026R-25 + R-11 + R-11 LS0.0370.0260.0390.039Owens Corning 10015581-J (Sept 2026)

FC means filled cavity with R-5 thermal blocks; LS means liner system with R-3 thermal blocks (Owens Corning footnote b). U-factors are in Btu per hour, square foot and degree Fahrenheit. The prescriptive 90.1-2022 wall entries are continuous insulation only: R-9.8 c.i. in zones 0 to 3, R-15.8 c.i. in zone 4, R-19 c.i. in zones 5 and 6, R-22.1 c.i. in zone 7 and R-25 c.i. in zone 8.

Space class moves the target more than the edition does. The MBMA COMcheck FAQ (January 2024) says a warehouse with no air conditioning and heating below the conditioned threshold in 90.1-2019 Table 3.2 can be semiheated while its office stays conditioned, and that any air conditioning makes a space conditioned. A semiheated zone 4 wall may reach U-0.162, which a single compressed R-13 blanket meets.

We could not open the final 2024 IECC tables: the ICC code viewer returned a CAPTCHA on October 20, 2026. The 2024 IECC development text in ICC code change file CED1-100-22 carries the same metal building rows as the 2021 IECC (roof U-0.035 in zones 0 to 5, wall U-0.052 in zone 4), so confirm the adopted text before you rely on it.

Which metal roof insulation systems pass the code?

In climate zones 4 to 8, only liner systems, filled cavities, or blankets topped with continuous insulation reach the ASHRAE 90.1-2022 roof limits. Appendix A, as reproduced by Owens Corning in September 2026, rates one R-19 blanket under a standing seam roof with R-3 thermal blocks at U-0.082, against a zone 4 limit of U-0.037.

Roof systemInsulation (rated R)Thermal blockAssembly U-factorZone 4 conditioned, 90.1-2022 (U-0.037)Source
Through-fastened, single layerR-10None0.184FailsOwens Corning 10015581-J (Sept 2026)
Through-fastened, single layerR-19None0.151FailsOwens Corning 10015581-J (Sept 2026)
Through-fastened + continuous insulationR-19 + R-19 c.i.None0.039FailsOwens Corning 10015581-J (Sept 2026)
Through-fastened + continuous insulationR-19 + R-22.1 c.i.None0.035PassesOwens Corning 10015581-J (Sept 2026)
Standing seam, single layerR-19R-30.082FailsOwens Corning 10015581-J (Sept 2026)
Standing seam, double layerR-19 + R-19R-30.060FailsOwens Corning 10015581-J (Sept 2026)
Standing seam, single layer + c.i.R-19 + R-19 c.i.R-30.032PassesOwens Corning 10015581-J (Sept 2026)
Filled cavityR-19 + R-11R-50.037PassesOwens Corning 10015581-J (Sept 2026)
Liner systemR-19 + R-11None0.040FailsOwens Corning 10015581-J (Sept 2026)
Liner systemR-19 + R-11R-30.037PassesOwens Corning 10015581-J (Sept 2026)
Liner systemR-25 + R-11R-30.031PassesOwens Corning 10015581-J (Sept 2026)
Liner systemR-25 + R-11 + R-11R-30.026PassesOwens Corning 10015581-J (Sept 2026)
Metal roof assembly U-factor by insulation systemBar chart: through-fastened R-19 roof U-0.151, standing seam R-19 U-0.082, R-19 + R-19 U-0.060, liner systems U-0.037 to U-0.026, against a zone 4 limit of U-0.037.Btu/h per sq ft per FThrough-fastened, R-190.15Standing seam, R-19, R-3 block0.08Standing seam, R-19 + R-19, R-3 block0.06Zone 4 limit, 90.1-20220.04Liner system, R-19 + R-11, R-3 block0.04Liner system, R-25 + R-11, R-3 block0.03Liner system, R-25 + R-11 + R-11, R-3 bloc0.03
Only the liner systems reach the zone 4 limit of U-0.037; a through-fastened R-19 roof is 4.1 times it. Source: Owens Corning 10015581-J reproducing ASHRAE 90.1-2022, accessed October 20, 2026.

A liner system hangs a continuous fabric below the purlins and lays uncompressed unfaced insulation on it, so the blanket is not crushed over each purlin. Owens Corning’s assembly notes require a minimum R-3 thermal spacer block (R-5 for filled cavity) unless the assembly U-factor proves compliance, plus a standing seam clip leaving at least 1.5 in between the purlin top and the panel underside.

Two limits catch bidders. The MBMA COMcheck FAQ says COMcheck gives no extra credit above R-47 of cavity insulation in a liner system with thermal blocks, and that thermal spacer blocks do not count as continuous insulation because they are not continuous across the assembly. A through-fastened roof can still pass with continuous insulation or a liner assembly from 90.1-2019 Table A2.3.3.

Which metal building wall systems pass?

A metal building wall in climate zone 4 needs U-0.060 under ASHRAE 90.1-2022 or U-0.052 under the 2021 IECC. A single R-13 blanket compressed between girts and panels rates U-0.162, so a code wall needs continuous board insulation, an uncompressed cavity fill with a thermal break strip, or two layers (Owens Corning, 2026).

Wall systemInsulation (rated R)Assembly U-factorZone 4, 90.1-2022 (U-0.060)Zone 4, 2021 IECC (U-0.052)Source
Single layer, compressedR-130.162FailsFailsOwens Corning 10015581-J (Sept 2026)
Single layer, compressedR-190.147FailsFailsOwens Corning 10015581-J (Sept 2026)
Compressed + continuous insulationR-13 + R-9.8 c.i.0.063FailsFailsOwens Corning 10015581-J (Sept 2026)
Continuous insulation onlyR-15.8 c.i.0.060PassesFailsOwens Corning 10015581-J (Sept 2026)
Compressed + continuous insulationR-13 + R-13 c.i.0.052PassesPassesOwens Corning 10015581-J (Sept 2026)
Single layer in cavity, R-0.375 stripR-250.059PassesFailsOwens Corning 10015581-J (Sept 2026)
Single layer in cavity, R-0.75 stripR-300.052PassesPassesOwens Corning 10015581-J (Sept 2026)
Double layerR-25 + R-100.047PassesPassesOwens Corning 10015581-J (Sept 2026)

Insulated metal panels (IMPs) need their own U-factor. The MBMA COMcheck FAQ states that IMPs do not qualify as continuous insulation because the metal side-joinery at each joint forms a partial thermal bridge, and that 90.1 did not recognize IMPs as cladding before the 2022 edition. The FAQ’s route is to enter the IMP maker’s U-factor under COMcheck’s “Other U-Factor Option”.

How much heat does each roof system lose? A worked example

Heat flow through a roof equals U-factor times area times the inside-to-outside temperature difference. For a 10,000 sq ft conditioned roof in zone 4, with 70 F inside and 20 F outside, a through-fastened R-19 blanket (U-0.151) passes 75,500 Btu per hour, while the code-minimum liner system (U-0.037) passes 18,500 Btu per hour.

Roof systemU-factor (Owens Corning 2026)Area (sq ft)Temperature difference (F)Heat flow (Btu/h)Multiple of zone 4 limit
Through-fastened, R-190.15110,0005075,5004.1x
Standing seam, R-19, R-3 block0.08210,0005041,0002.2x
Standing seam, R-19 + R-19, R-3 block0.06010,0005030,0001.6x
Liner system, R-19 + R-11, R-3 block (zone 4 limit)0.03710,0005018,5001.0x
Liner system, R-25 + R-11, R-3 block0.03110,0005015,5000.8x
Liner system, R-25 + R-11 + R-11, R-3 block0.02610,0005013,0000.7x

The arithmetic is a CB&C calculation (Q = U x A x temperature difference) from published Appendix A U-factors; it is an illustration, not a design heating load. The inverse of U-0.151 is an assembly R-value of about 6.6, roughly one third of the R-19 printed on the roll, because the blanket is crushed to near zero thickness over every purlin.

Insulation pricing moves with the system, not just the R-value: a liner system adds the fabric, banding and a second layer, and continuous insulation adds rigid board and longer fasteners. We found no public record that prices metal building insulation alone per square foot: a screen of about 6,000 federal insulation awards on USAspending.gov on October 26, 2026 turned up only whole-roof replacements and loose-roll purchases with no area. For the whole building, the dated federal price records are in our guide to steel building prices. The BLS producer price index for insulation materials (WPU1392) rose 2.7% from September 2025 to September 2026 (preliminary). Ask each bidder for the assembly name and its Appendix A U-factor so the quotes compare like for like, as set out in our guide on how to compare construction bids.

What do NAIMA 202 and the roll label prove?

NAIMA 202 is the product standard for flexible fiber glass insulation made to be laminated and used in metal building roofs and walls. Its 2021 edition measures R-value at a 75 F mean temperature under ASTM C653 and requires a three-roll average of at least 103% of the nominal value, but the rating covers the blanket alone, not the installed assembly.

NAIMA 202 requirement (2021 edition)ValueSection
Common nominal R-valuesR-10, R-11, R-13, R-16, R-19, R-25, R-306.1
Minimum R per inspection (three-roll average)103% of nominal (R-19 roll: 19.6)6.1.1, Table 1
Flame spread / smoke developed index, unfaced25 / 50 maximum (ASTM E84 or UL 723)6.2.1
Water vapor sorption0.2% by volume maximum6.3
Independent lab testingQuarterly12.1
Marking on the insulationManufacturer or product name, NAIMA 202, R-value13.1
Package compression ratio after laminationLess than 5.5:1; 5.0:1 or less for best recoveryX1.3
Storage after lamination7 days maximum recommendedX1.6

NAIMA 202 Section 1.3 sends post-lamination R-value certification to the NIA Certified Faced Insulation Standard, and the NAIMA installation guide (Pub. MB316, 2006) says rolls should arrive with the certification label, or show NAIMA 202 ink-jet printed on the blanket if opened. Section 1.4 is the line to show a bidder: rated R-values exclude facings, air films, compression at framing and metal fasteners.

ASHRAE interpretation IC 90.1-2016-9 with the R-19 5.45 inch reference thickness and the answer No boxed
ASHRAE IC 90.1-2016-9 (approved October 12, 2019), boxed: Table A9.4.6.1 assumes 5.45 in for R-19, and the answer to the rated-R-value-only reading is No. Source: ashrae.org PDF, pages 1 and 2, accessed October 20, 2026.

The ASHRAE interpretation IC 90.1-2016-9, approved October 12, 2019, shows why thickness still matters. It notes that 90.1 Table A9.4.6.1 assumes 5.45 in for an R-19 metal building blanket, while makers rate R-19 at 6.00 in and 6.38 in, then answers “No” to a proposed reading that the rated R-value alone, at any thickness, satisfies Appendix A. Ask the designer which Appendix A assembly the COMcheck report uses and confirm the delivered product matches it.

How do you stop condensation in a steel building?

Condensation forms when warm, moist interior air reaches a surface colder than its dew point, and steel purlins and panels get cold fast. The MBMA Condensation Fact Sheet says problems are most likely where temperatures often drop to 35 F or below for long periods, and that 70 F air at 50% relative humidity has a 50 F dew point.

Relative humidityDew point at 60 F inside (F)Dew point at 70 F inside (F)Source
30%2937MBMA Table C-1
40%3545MBMA Table C-1
50%4150MBMA Table C-1
60%4655MBMA Table C-1
70%5060MBMA Table C-1
80%5464MBMA Table C-1
90%5767MBMA Table C-1
Dew point of indoor air by relative humidityLine chart: at 70 F inside, dew point rises from 37 F at 30% humidity to 50 F at 50% and 67 F at 90%; at 60 F inside, from 29 F to 57 F.20.030.040.050.060.070.0dew point, F30%40%50%60%70%80%90%70 F inside60 F inside
At 70 F and 50% relative humidity, any steel surface below 50 F condenses water. Source: MBMA Condensation Fact Sheet, Table C-1, accessed October 20, 2026.

The vapor retarder facing keeps that moist air out of the blanket. The MBMA sheet reports NAIMA’s recommendation of a facing rated at 0.10 perm or less under ASTM E96, and NAIMA’s installation guide lists minimum temperatures for handling each facing.

FacingPerm rating (NAIMA MB316)Perm rating (MBMA Table C-2)Minimum install temperature (F)Meets 0.10 perm?
White vinyl1.01.0 to 1.340No
Polypropylene/scrim/kraft (PSK)0.02 to 0.090.02 to 0.0920Yes
Foil/scrim/kraft (FSK)0.020.0210Yes
Polypropylene/scrim/foil (PSF)0.02Not listed20Yes
Vinyl/scrim/metallized polyester (VRP)0.020.0220Yes

High humidity tightens every rule. The MBMA sheet says buildings above 30% relative humidity need careful condensation design and those above 50% are especially prone, naming pools, ice rinks, wineries, livestock barns, highway maintenance garages and waste processing. For them it asks for a facing below 0.05 perm with sealed seams, and says folding and stapling seams is not recommended.

Ventilation is the second control. The same sheet sizes it by air changes: a 100 by 250 by 30 ft light manufacturing building holds 750,000 cu ft, so 5 air changes per hour needs 62,500 CFM. Cold-side cavities need 1 sq ft of free vent area per 300 sq ft of cavity, and cold storage buildings need a vapor retarder on both sides of the insulation.

How should steel building insulation be installed and checked?

Faced metal building insulation goes in as the roof and wall panels go on, so most defects are fixed on the day or never. The NAIMA installation guide (MB316) and the MBMA sheet give the measurements: rolls run eave to eave with 12 in extra at each end, tabs are stapled about every 4 in, and punctures are patched with the supplier’s tape.

Steel building insulation install and check sequence Eight steps from confirming the code target to inspecting the sealed vapor retarder, with the NAIMA and MBMA values for each. Install and check sequence for faced metal building insulation 1. Confirm the target Assembly U-factor, climate zone and space class on the drawings or COMcheck report 2. Check the rolls on arrival NAIMA 202 and the R-value printed on the blanket; certification label on the roll 3. Check the facing perm rating 0.10 perm or less; below 0.05 perm above 50% RH; not plain white vinyl (1.0 to 1.3) 4. Store dry, install warm enough Off the ground and covered; vinyl facings 40 F minimum, PSK 20 F, FSK 10 F 5. Set thermal spacer blocks R-3 on standing seam and liner systems, R-5 on filled cavity; clip gap 1.5 in or more 6. Roll eave to eave 12 in extra at each end, facing toward the interior, taut but not overstretched 7. Seal every lap Two 3 in tabs stapled about every 4 in, or a glued 6 in tab; no fold-and-staple above 50% RH 8. Repair and inspect Supplier's repair tape on punctures; inspect the vapor retarder after all trades finish
Install and check sequence compiled by CB&C from NAIMA MB316, NAIMA 202 (2021), the MBMA Condensation Fact Sheet and Owens Corning 10015581-J (accessed October 20, 2026).
  1. Confirm the target. Read the assembly U-factor, climate zone and space class on the drawings or the COMcheck report.
  2. Check the rolls on arrival. Look for NAIMA 202 and the R-value printed on the blanket and the certification label on the roll (NAIMA 202 Section 13.1; MB316).
  3. Check the facing perm rating. 0.10 perm or less; below 0.05 perm above 50% relative humidity; not plain white vinyl at 1.0 to 1.3 perm (MBMA).
  4. Store dry, install warm enough. Keep packages off the ground and covered; vinyl facings need 40 F minimum, PSK 20 F and FSK 10 F (MB316 Table 2).
  5. Set thermal spacer blocks. R-3 on standing seam and liner systems, R-5 on filled cavity, with a clip gap of 1.5 in or more (Owens Corning, 2026).
  6. Roll eave to eave. Add 12 in at each end, face the vapor retarder toward the interior, and keep the blanket taut without overstretching it (MB316).
  7. Seal every lap. Staple two 3 in tabs about every 4 in, 1/4 to 1/2 in from the edge, or glue a single 6 in tab; do not fold and staple above 50% relative humidity (MB316; MBMA).
  8. Repair and inspect. Patch punctures with the supplier’s repair tape and inspect the vapor retarder after all trades finish (MBMA).

Air leakage is checked separately from insulation. MBMA publishes guidance on whole-building air leakage testing, and the 2024 IECC path in Section C401.2.1 includes Section C408 commissioning, which some cities, Phoenix among them, made optional in 2025. Our building commissioning guide covers when C408 applies and who signs it.

Which steel building insulation system fits your building?

Pick the system from four facts: the code path, the space class, the climate zone and the interior humidity. Once those are known, ASHRAE 90.1 Appendix A Tables A2.3.3 (roofs) and A3.2.3 (walls) name assemblies that meet each U-factor, and the MBMA COMcheck FAQ says those tables need no alternative-methods request from the building official.

If your building isThen the roof target isA listed system that meets itSource
Conditioned, zone 0 to 3, 90.1-2022 pathU-0.041R-10 + R-19 filled cavity, R-5 blocksOwens Corning 10015581-J (Sept 2026)
Conditioned, zone 0 to 5, 2021 IECC pathU-0.035R-19 + R-22.1 c.i. on a through-fastened roof (U-0.035)Owens Corning 10015581-J (Sept 2026)
Conditioned, zone 4 or 5, 90.1-2022U-0.037R-19 + R-11 or R-25 + R-8 liner system, R-3 blocksOwens Corning 10015581-J (Sept 2026)
Conditioned, zone 6, 90.1-2022U-0.031R-25 + R-11 liner system, R-3 blocksOwens Corning 10015581-J (Sept 2026)
Conditioned, zone 8, 90.1-2022U-0.026R-25 + R-11 + R-11 liner system, R-3 blocksOwens Corning 10015581-J (Sept 2026)
Semiheated, zone 4, no air conditioningU-0.082R-19 single layer, standing seam, R-3 blocksOwens Corning 2026; MBMA FAQ 2024
Above 50% relative humiditySame U-factorFacing below 0.05 perm, sealed (not folded and stapled) seamsMBMA Condensation Fact Sheet
Cold storageSame U-factorVapor retarder on both sides; foil-faced board with joints staggered 6 in or moreMBMA Condensation Fact Sheet
System not in Appendix A (spray foam, IMP)Same U-factorU-factor tested to ASTM C1363 or modeled, entered as Other U-FactorMBMA COMcheck FAQ 2024
Which steel building insulation target applies Six-question flowchart from the adopted energy code to the climate zone U-factor, assembly table, COMcheck and vapor retarder rating. From adopted code to insulation system: six questions 1. Which energy code has the state or city adopted? Check the CB&C energy code by state registry No statewide code (10 states) Use the local code or the owner's specification 2. Pick one path: IECC Chapter 4 or ASHRAE 90.1 IECC Section C401.2 allows either Mix 90.1 envelope, IECC trades? Not allowed: follow one path for the whole building 3. Any air conditioning in the space? Yes: conditioned. No, low heat: may be semi-heated Semi-heated (90.1 Table 3.2)? Use the semiheated column of the 90.1 tables 4. Find the climate zone (IECC Table C301.1) Read the roof and wall U-factor for that zone Example: zone 4, 90.1-2022 Conditioned roof U-0.037, wall U-0.060 5. Appendix A assembly at or below the U-factor? Tables A2.3.3 / A3.2.3; yes: enter it in COMcheck Not listed or above the limit? Tested U-factor (ASTM C1363) or change the system 6. Interior RH above 50% or cold storage? No: facing rated 0.10 perm or less Yes Facing below 0.05 perm, sealed seams; both sides if cold storage
Decision path compiled by CB&C from IECC Section C401.2 (2024, via City of Phoenix), NC OSFM, the MBMA COMcheck FAQ (2024), MBMA Condensation Fact Sheet and Owens Corning 10015581-J (accessed October 20, 2026).
  1. Find the energy code the state or city has adopted; in the 10 states with no statewide code, use the local code or the owner’s specification.
  2. Pick one path, IECC Chapter 4 or ASHRAE 90.1, under IECC Section C401.2, and follow it for the whole building.
  3. Decide whether each space is conditioned (any air conditioning) or semiheated under 90.1 Table 3.2.
  4. Find the climate zone in IECC Table C301.1 and read the roof and wall U-factor; in zone 4 under 90.1-2022, a conditioned roof is U-0.037 and a wall U-0.060.
  5. Choose an Appendix A assembly from Tables A2.3.3 or A3.2.3 at or below that U-factor and enter it in COMcheck; if it is not listed, use a tested U-factor (ASTM C1363) or change the system.
  6. If interior humidity exceeds 50% or the building is cold storage, specify a facing below 0.05 perm with sealed seams, and vapor retarders on both sides for cold storage; otherwise 0.10 perm or less.

The DOE COMcheck tool produces the compliance report, and the MBMA FAQ notes that it may need a registered design professional’s signature under 2021 IECC Section C103.3. For the builder side of a pre-engineered package, see our guide to metal building contractors. For a distribution building where the office and the warehouse floor carry different targets, see warehouse construction.

What do common insulation guides get wrong?

Most top-ranking steel building insulation pages in October 2026 were seller blogs and spun content listing insulation types without a single U-factor or code section. Five claims recur, and each one diverges from the primary documents on what a code inspector or a condensation problem will measure.

What guides sayWhat the primary source saysSource
Pick a fiberglass blanket by its R-value (batts cited at about R-13)Under a through-fastened roof an R-19 blanket rates U-0.151, 4.1 times the zone 4 limit of U-0.037Owens Corning 2026 (90.1-2022 Appendix A)
Install a vapor barrierFacing should be 0.10 perm or less; white vinyl at 1.0 to 1.3 perm is not an effective vapor retarderMBMA Condensation Fact Sheet
Installed cost is $2.10 to $12.00 per sq ft (no source named)No primary source found; cost follows the assembly (liner, blocks, c.i.); insulation PPI +2.7% Sept 2025 to Sept 2026BLS WPU1392
The R-value on the label settles complianceASHRAE answered No to rated R-value alone at any thickness; Table A9.4.6.1 assumes 5.45 in for R-19ASHRAE IC 90.1-2016-9
Thermal blocks or insulated panels count as continuous insulationNeither qualifies as c.i.; IMPs need the maker’s U-factorMBMA COMcheck FAQ 2024

The roof and wall assemblies above sit on the frame described in our pre-engineered metal building guide; for red iron versus tubular framing, see our red iron building guide.

How we compiled this

We compiled this in October 2026 from 11 primary documents (the Owens Corning bulletin reproducing the ASHRAE 90.1 and IECC metal building tables, ASHRAE interpretation IC 90.1-2016-9, two NAIMA documents, three MBMA publications, the 2024 IECC text quoted by the City of Phoenix, a North Carolina fire marshal ruling, an ICC code change file and BLS price data), plus DOE adoption data from our state registry and a USAspending.gov screen for priced insulation records on October 26, 2026. We tested no product and installed nothing; the ICC code viewer (CAPTCHA) and the PDF of MBMA’s second-edition energy guide (404 error) were unreachable, so 2024 IECC values come from development text. CB&C is a matching service, not an engineer, so this is not design advice: the project’s registered design professional decides compliance, as our editorial standards explain.

Frequently asked questions

What R-value do I need to insulate a steel building?

The code sets a U-factor for the whole assembly, not one R-value. Under ASHRAE 90.1-2022, a conditioned zone 4 roof needs U-0.037, met by an R-19 + R-11 liner system with R-3 thermal blocks; zone 8 needs U-0.026, met by R-25 + R-11 + R-11. A single R-19 blanket under a through-fastened roof rates U-0.151 (Owens Corning, 2026).

Do I need a vapor retarder in a metal building?

Faced fiber glass already carries one, and its rating matters. The MBMA Condensation Fact Sheet reports NAIMA’s recommendation of a facing at 0.10 perm or less and calls white vinyl at 1.0 to 1.3 perm not an effective vapor retarder. Buildings above 50% relative humidity need a facing below 0.05 perm with sealed seams.

Can I use spray foam or insulated metal panels instead of fiberglass?

Yes, if the assembly has a documented U-factor. ASHRAE 90.1 Appendix A metal building values use fiberglass reference data (Table A9.4.6.1), so other systems need a U-factor tested to ASTM C1363 or thermally modeled, entered under COMcheck’s Other U-Factor Option. The MBMA COMcheck FAQ (2024) says insulated metal panels do not count as continuous insulation.

Does the warehouse area need the same insulation as the office?

Not always. The MBMA COMcheck FAQ (2024) says a warehouse with no air conditioning and heating below the conditioned threshold in 90.1-2019 Table 3.2 can be semiheated. In zone 4, a semiheated metal roof may reach U-0.082 against U-0.037 for a conditioned one. Any air conditioning makes the space conditioned.

Why does my metal building roof drip?

Moist interior air is reaching steel below its dew point. At 70 F and 50% relative humidity the dew point is 50 F, per MBMA Table C-1, and cold purlins or panels fall below that in winter. Check for torn or unsealed facing laps, a facing above 0.10 perm, and too little ventilation; MBMA’s sizing example uses 5 air changes per hour.

Do thermal blocks count as continuous insulation?

No. The MBMA COMcheck FAQ (2024) says thermal spacer blocks do not satisfy the prescriptive continuous insulation requirement because they are not continuous across the assembly. They still matter: Owens Corning’s 2026 guide shows an R-19 + R-11 liner system improving from U-0.040 to U-0.037 when R-3 blocks are added, which is the zone 4 pass mark.

What does NAIMA 202 on the insulation mean?

It means the blanket was made to the NAIMA 202 standard for fiber glass laminated for metal buildings, tested quarterly by an independent laboratory, with a three-roll average R-value of at least 103% of nominal (2021 edition). Certification after lamination falls under the NIA Certified Faced Insulation Standard, and the rating excludes facings and compression at the framing.

How much does it cost to insulate a steel building?

We found no public record that prices metal building insulation alone per square foot; a screen of about 6,000 federal insulation awards on October 26, 2026 found only whole-roof jobs. Ask each bidder to price insulation as its own line, naming the Appendix A assembly and its U-factor. Material prices moved little: BLS insulation materials rose 2.7% in the 12 months to September 2026.

Sources

Last reviewed October 2026 by the CB&C Editorial Team. See our editorial standards.