Occupancy Classification: IBC 2024 Groups, Occupant Load and What Each Group Triggers

Unfinished multi-tenant commercial building with metal stud tenant walls and sprinkler mains under steel joists

Occupancy classification is the building code’s label for how a space is used: the 2024 International Building Code (IBC) sorts every room into 10 groups and 26 sub-groups, and that letter sets sprinklers, exits and egress width.

Key takeaways

  • The 2024 IBC lists 10 occupancy groups split into 26 classifications, from A-1 theaters to U sheds, and a use the code does not list goes in the group it most nearly resembles (IBC 2024 Section 302.1).
  • An assembly building or tenant space with fewer than 50 occupants is Group B, not Group A, and an accessory assembly room under 750 sq ft can also stay Group B (Sections 303.1.1 and 303.1.2).
  • A secondary use counts as an accessory occupancy only while all accessory uses together take no more than 10% of the story’s floor area (IBC 2024 Section 508.2.3).
  • Occupant load is floor area divided by the Table 1004.5 factor: 150 gross sq ft per person for offices, 60 gross for retail floors and 15 net for dining at tables and chairs (IBC 2024 Table 1004.5).
  • A Group A-2 restaurant needs sprinklers throughout its story once its fire area exceeds 5,000 sq ft or holds 100 or more people, while M, F-1, S-1 and E trigger above a 12,000 sq ft fire area (IBC 2024 Section 903.2).
  • Changing an office (egress hazard category 4) into a restaurant (category 3) is a move to a higher hazard, so the egress must meet full IBC Chapter 10 rules (IEBC 2024 Section 1011.5.1).

What is occupancy classification?

Occupancy classification is “the formal designation of the primary purpose of the building, structure or portion thereof” under IBC 2024 Section 302.1. The building official assigns each space a group by its fire hazard and the risk to the people inside, and that group then sets the occupant load factor, sprinkler trigger, exit count, travel distance, fire separations and allowable height and area.

The label applies room by room, not only to the whole building. Section 302.1 says a structure is classified into one or more groups, that a room used for different purposes at different times must meet the rules of each use, and that buildings with several groups follow Section 508. The full text is free to read in IBC 2024 Chapter 3 on ICC Digital Codes.

Your state or city enforces its own adopted edition, often with amendments. Washington, for example, adds a “billiard table/game table area” factor of 50 gross sq ft per person to the occupant load table, a row the 2024 model code does not carry (WAC 51-50-1004, effective March 16, 2024). This guide quotes the 2024 IBC and the 2024 International Existing Building Code (IEBC) and is a reading of the model code, not legal or design advice.

RuleNumberSource
Occupancy groups and classifications10 groups, 26 classificationsIBC 2024 302.1
Assembly use becomes Group A at50 occupantsIBC 2024 303.1.1
Accessory assembly room stays Group BUnder 50 occupants or under 750 sq ftIBC 2024 303.1.2
Accessory occupancy cap10% of the story’s floor areaIBC 2024 508.2.3
Business (office) occupant load factor150 gross sq ft per personIBC 2024 Table 1004.5
Most occupants allowed in a one-exit A, B, E, F, M or U room49IBC 2024 Table 1006.2.1
Egress capacity, doors and corridors0.2 in per occupantIBC 2024 1005.3.2
Egress capacity, stairways0.3 in per occupantIBC 2024 1005.3.1
Group A-2 sprinkler triggerFire area over 5,000 sq ft or 100 occupantsIBC 2024 903.2.1.2
A-1, A-3, A-4, E, F-1, M, S-1 sprinkler triggerFire area over 12,000 sq ft (plus other conditions)IBC 2024 903.2
Exits per story2 up to 500 occupants, 3 up to 1,000, 4 aboveIBC 2024 Table 1006.3.3
Plumbing fixture recount after a change of occupancyStory occupant load up more than 20%IEBC 2024 1009.1

What are the 10 IBC occupancy groups?

IBC 2024 Section 302.1 lists 10 occupancy groups: Assembly (A), Business (B), Educational (E), Factory and Industrial (F), High Hazard (H), Institutional (I), Mercantile (M), Residential (R), Storage (S) and Utility and Miscellaneous (U). Six groups split into numbered sub-groups by use or hazard, which gives 26 classifications. The table lists each one with examples taken from the code text.

GroupWhat it coversExamples named in the codeIBC 2024 section
A-1Assembly, usually with fixed seats, for performing arts or filmsTheaters, concert halls, TV and radio studios with an audience303.2
A-2Assembly for food or drinkRestaurants with their kitchens, bars, banquet halls, nightclubs, casino gaming areas303.3
A-3Worship, recreation, amusement and other assemblyPlaces of worship, libraries, museums, courtrooms, gyms and pools without spectator seating, transit waiting areas303.4
A-4Indoor sports with spectator seatingArenas, skating rinks, swimming pools, tennis courts303.5
A-5Outdoor activitiesStadiums, grandstands, bleachers, amusement park structures303.6
BOffice, professional and service transactionsOffices, banks, outpatient clinics, ambulatory care, education above grade 12, labs, car washes, kitchens not tied to a restaurant up to 2,500 sq ft304.1
EEducation through grade 12 for 6 or more peopleSchools; day care for more than 5 children older than 2 1/2305.1, 305.2
F-1Moderate-hazard manufacturingBakeries, woodworking, vehicles, electronics, food processing over 2,500 sq ft306.2
F-2Low-hazard manufacturing of noncombustible goodsBrick, ceramics, glass, ice, metal fabrication, beverages up to 20% alcohol306.3
H-1Detonation hazardExplosives, Class 4 oxidizers, detonable unstable materials307.3
H-2Deflagration or accelerated burningFlammable liquids in open systems or above 15 psig, combustible dust processes, Category 1A flammable gases307.4
H-3Materials that readily support combustionFlammable liquids in closed systems at 15 psig or less, flammable solids, consumer fireworks 1.4G307.5
H-4Health hazardsCorrosives, toxic and highly toxic materials307.6
H-5Semiconductor fabricationFabs and comparable research areas using hazardous production materials307.7
GroupWhat it coversExamples named in the codeIBC 2024 section
I-124-hour custodial care for more than 16 residentsAssisted living, group homes, halfway houses308.2
I-224-hour medical care for more than 5 people who cannot self-evacuateHospitals, nursing homes, psychiatric hospitals308.3
I-3More than 5 people under restraint or securityJails, prisons, detention centers308.4
I-4Day care for more than 5 people of any age, under 24 hoursAdult day care, infant day care308.5
MDisplay and sale of goods with public accessDepartment stores, drug stores, markets, fuel stations309.1
R-1Transient sleepingHotels, motels, lodging houses with more than 5 guestrooms310.2
R-2Permanent sleeping, more than 2 dwelling unitsApartments, dormitories, live/work units310.3
R-3Not more than 2 dwelling units; small care homesDuplexes built under the IBC, care for 5 or fewer310.4
R-424-hour custodial care for 6 to 16 residentsSmall assisted living and group homes310.5
S-1Moderate-hazard storageSelf-storage, furniture, lumber, tires, paper, repair garages311.2
S-2Low-hazard storage of noncombustiblesParking garages, frozen food, glass, metal parts311.3
UAccessory and miscellaneous structuresBarns, sheds, private garages, fences over 7 ft, towers, tanks312.1

Our sector guides apply single groups in depth. A sanctuary is Group A-3, with a 783-person occupant load worked through in our church construction guide.

Mini-storage is Group S-1 under Section 311.2, and the sprinkler and conversion rules that follow are in our self-storage construction guide. Hotels are Group R-1 under Section 310.2, as covered in our hotel construction guide.

Where do the obvious answers go wrong?

Most misclassifications come from thresholds buried inside Chapter 3. An assembly use under 50 occupants is Group B, a college is Group B rather than E, and the same assisted living use is R-4 at 16 residents but I-1 at 17. The table lists the lines in IBC 2024 Sections 303 to 311 that move a use from one group to another.

UseAt or below the lineAbove the lineIBC 2024 section
Assembly building or tenant spaceUnder 50 occupants: Group B50 or more: Group A303.1.1
Assembly room accessory to another useUnder 50 occupants or under 750 sq ft: Group B or part of the main useOtherwise: Group A303.1.2
Religious classrooms and auditoriumsUnder 100 per room: part of the A-3 worship use100 or more: classified on their own303.1.4, 305.1.1
EducationThrough grade 12, 6 or more people: Group EAbove grade 12: Group B305.1, 304.1
Child day care5 or fewer children: part of the main useMore than 5 older than 2 1/2: E; more than 5 aged 2 1/2 or under: I-4, or E if up to 100 children on the exit discharge level with an exterior door from each room305.2, 308.5, 308.5.1
Custodial care residence5 or fewer: R-36 to 16: R-4; more than 16: I-1308.2.3, 308.2.4, 310.5
Commercial kitchen not serving a restaurant2,500 sq ft or less: Group BMore than 2,500 sq ft: Group F-1304.1, 306.2
Lodging house5 or fewer guestrooms: R-3More than 5: R-1310.2, 310.4
Storage room accessory to another usePart of the main occupancyStand-alone storage: S-1 or S-2311.1.1
Hazardous materialsWithin the maximum allowable quantity per control area: stays in its groupAbove it: Group H307.1

Restaurants cross the 50-person line more often than any other tenant, because Table 1004.5 counts dining by floor area, not by chairs: 750 sq ft net of dining at 15 net sq ft per person is already 50 occupants and Group A-2. Fit-out scopes for that use are covered in our restaurant build-out contractors guide.

Health care splits across three groups. A hospital is Group I-2, Condition 2, when it may provide surgery, emergency care or obstetrics (Section 308.3.1.2), while outpatient clinics are Group B, and hospitals paid by Medicare must also meet the 2012 NFPA 101 Life Safety Code (42 CFR 482.41). Hospital projects are covered in our healthcare construction guide, and clinics in our medical office construction guide.

How do you choose an occupancy classification for a mixed-use building?

When one building holds two or more groups, IBC 2024 Section 508 offers three methods: accessory occupancies (secondary uses that together take no more than 10% of a story), nonseparated occupancies (the strictest group’s rules apply throughout) and separated occupancies (fire barriers rated under Table 508.4). One building can combine methods, and each trades wall cost against sprinkler, height and area limits.

Three-column comparison of IBC Section 508 accessory, nonseparated and separated occupancy methodsAccessorySection 508.2Size limitNot over 10% of the storyand Table 506.2 NS areaHeight and areaSet by the mainoccupancySeparationNone (H-2 to H-5 andsleeping units excepted)Sprinklers, alarmsEach space by itsown groupNonseparatedSection 508.3Size limitNoneHeight and areaMost restrictive groupfor the whole buildingSeparationNone (sameexceptions)Sprinklers, alarmsMost restrictive rule overthe whole nonseparated areaSeparatedSection 508.4Size limitNoneHeight and areaSum of actual / allowablearea ratios per story: 1 or lessSeparationFire barriers per Table 508.4(A to B sprinklered: 1 hour)Sprinklers, alarmsMost restrictive rule withineach fire-barrier-bounded area
The three IBC 2024 Section 508 methods compared on size limit, height and area, separation and Chapter 9 systems. Source: ICC, 2024 International Building Code Sections 508.2 to 508.4, accessed November 2, 2026.
MethodQualifies whenHeight and areaSeparationSprinklers and alarms (Chapter 9)Source
AccessoryAll accessory uses together are 10% or less of the story and each is within its Table 506.2 nonsprinklered areaSet by the main occupancyNone, except H-2 to H-5 and dwelling or sleeping unitsEach space by its own groupIBC 2024 508.2
NonseparatedAny mixMost restrictive group for the whole buildingNone, same exceptionsMost restrictive rule over the whole nonseparated areaIBC 2024 508.3
SeparatedAny mixSum of actual area divided by allowable area for each group, per story, 1 or lessFire barriers (Section 707) or horizontal assemblies (Section 711) per Table 508.4Most restrictive rule within each area bounded by fire barriersIBC 2024 508.4

What is the 10% accessory occupancy rule?

Under Section 508.2.3, accessory occupancies may not exceed 10% of the floor area of the story they sit on, and each must stay within its Table 506.2 nonsprinklered area. A 3,000 sq ft office in a 40,000 sq ft Group S-1 warehouse is 7.5% of the story and, in a Type IIB building, well under the 23,000 sq ft nonsprinklered value for Group B, so it is accessory.

Being accessory removes the fire separation and keeps height and area on the warehouse’s S-1 rules, but the office is still classified as Group B for its own egress and occupant load (Section 508.2.1). The 40,000 sq ft S-1 fire area needs sprinklers anyway, because it exceeds 12,000 sq ft under Section 903.2.9. Shell, dock and slab decisions for that building type are in our warehouse construction guide.

How many hours of separation does Table 508.4 require?

Table 508.4 sets the fire barrier rating between separated groups in hours, with one value for buildings sprinklered throughout under NFPA 13 (Section 903.3.1.1) and a higher value, or “not permitted”, for buildings without. Assembly next to business or retail needs 1 hour sprinklered and 2 hours unsprinklered; H-1 may not share a building with any other group.

Groups side by sideSprinklered throughoutNot sprinkleredSource
A or E next to B, F-1, M or S-11 hour2 hoursIBC 2024 Table 508.4
A or E next to R1 hour2 hoursIBC 2024 Table 508.4
R next to B, F-1, M or S-11 hour2 hoursIBC 2024 Table 508.4
A or E next to F-2, S-2 or UNo separation1 hourIBC 2024 Table 508.4
I-2 next to A, E, B, M or R2 hoursNot permittedIBC 2024 Table 508.4
H-2 next to A or E3 hours4 hoursIBC 2024 Table 508.4
H-1 next to any other groupNot permittedNot permittedIBC 2024 Table 508.4; Section 508.1 exception 2

How do you calculate occupant load?

Divide the floor area of each space by the occupant load factor for its function in IBC 2024 Table 1004.5, then add the spaces that share an exit path. Offices use 150 gross sq ft per person, retail sales floors 60 gross, dining at tables and chairs 15 net and chairs-only assembly 7 net. Rooms with fixed seats count the seats instead (Section 1004.6).

Gross and net areas differ. Gross floor area runs to the inside of the exterior walls with no deduction for corridors, stairs, closets or interior walls; net floor area counts only the occupied area and leaves out corridors, stairways, toilet rooms, mechanical rooms and closets (IBC 2024 Chapter 2 definitions). Each function in a room is calculated on its own under Section 1004.3.

Function of spaceSq ft per occupantArea basisSource
Standing space5NetIBC 2024 Table 1004.5
Assembly, chairs only (not fixed)7NetIBC 2024 Table 1004.5
Assembly, tables and chairs15NetIBC 2024 Table 1004.5
Classroom20NetIBC 2024 Table 1004.5
Exhibit gallery and museum30NetIBC 2024 Table 1004.5
Day care35NetIBC 2024 Table 1004.5
Exercise rooms50GrossIBC 2024 Table 1004.5
Mercantile (sales floor)60GrossIBC 2024 Table 1004.5
Industrial areas100GrossIBC 2024 Table 1004.5
Outpatient areas100GrossIBC 2024 Table 1004.5
Institutional sleeping areas120GrossIBC 2024 Table 1004.5
Business areas150GrossIBC 2024 Table 1004.5
Commercial kitchens200GrossIBC 2024 Table 1004.5
Residential200GrossIBC 2024 Table 1004.5
Inpatient treatment areas240GrossIBC 2024 Table 1004.5
Storage, stock and shipping areas300GrossIBC 2024 Table 1004.5
Warehouses500GrossIBC 2024 Table 1004.5
Square feet per occupant by function of spaceBar chart of IBC 2024 occupant load factors from 5 sq ft per person standing to 500 sq ft in warehouses.sq ft per occupantStanding space (net)5Chairs only, not fixed (net)7Tables and chairs (net)15.0Classroom (net)20.0Exhibit gallery and museum (net)30.0Day care (net)35.0Exercise rooms (gross)50.0Mercantile sales floor (gross)60.0Industrial areas (gross)100Business areas (gross)150Commercial kitchens (gross)200Storage, stock, shipping (gross)300Warehouses (gross)500
Occupant load factors run from 5 net sq ft per person for standing space to 500 gross sq ft in warehouses. Source: ICC, 2024 International Building Code, Table 1004.5, accessed November 2, 2026.

Four rules adjust the arithmetic. The building official may approve the actual design headcount where it is lower (Section 1004.5 exception); an owner may raise the load up to 1 person per 7 sq ft if exits and fixtures are sized for it (Section 1004.5.1); benches count 1 person per 18 in and booths 1 per 24 in (Section 1004.6); and call centers use the actual count but not less than 1 per 50 gross sq ft (Section 1004.8).

Every assembly room must post its occupant load near the main exit (Section 1004.9). Fixed seating, standing areas and bars change that posted number, so the architect’s code summary should show each function and area line by line.

IBC 2024 Table 1004.5 occupant load factors with the Business areas 150 gross row boxed
IBC 2024 Table 1004.5 sets business areas at 150 gross sq ft per occupant (boxed). Source: ICC Digital Codes, 2024 International Building Code, Section 1004.5, page text saved November 2, 2026 and shown without site styling.

What does a 12,000 sq ft mixed-use building trigger?

Take an illustrative one-story, 12,000 sq ft building with a restaurant, a shop and an office suite. Table 1004.5 gives 267 occupants. The 164-person restaurant is Group A-2, and because it holds 100 or more people, Section 903.2.1.2 requires sprinklers throughout the story. The story needs 2 exits, and the restaurant’s doors need 32.8 in of capacity.

The building is a CB&C example built to show the arithmetic, not a real project. Areas are rounded to the nearest 100 sq ft, and each space is rounded up to a whole person; the code text sets no rounding rule, so confirm the plan reviewer’s convention.

StepInputArithmeticResultIBC 2024 rule
1. Dining room2,400 sq ft net, tables and chairs2,400 / 15160Table 1004.5
2. Restaurant kitchen800 sq ft gross800 / 2004Table 1004.5
3. Restaurant group160 + 4 = 164164 is 50 or moreGroup A-2303.1.1, 303.3
4. Retail sales floor4,800 sq ft gross4,800 / 6080Table 1004.5
5. Retail stockroom1,200 sq ft gross1,200 / 3004 (stays Group M as accessory storage)Table 1004.5, 311.1.1
6. Office suite2,800 sq ft gross2,800 / 150 = 18.719, Group BTable 1004.5, 304.1
7. Accessory test for the office2,800 of 12,000 sq ft23.3%Over 10%: not accessory508.2.3
8. Story occupant load164 + 84 + 19Sum2671004.2
9. SprinklersA-2 load of 164164 is 100 or moreRequired throughout the story903.2.1.2
10. Exits from the story267 occupants1 to 500 band2Table 1006.3.3
11. Exits from each tenant164 / 84 / 19Over 49?2 / 2 / 1Table 1006.2.1
12. Restaurant door capacity164 x 0.2 in32.8 inTwo 32 in doors give 64 in; losing one leaves 32 in, more than half of 32.81005.3.2, 1005.5, 1010.1.1
13. Shop door capacity84 x 0.2 in16.8 inThe 32 in minimum door width governs1005.3.2, 1010.1.1
14. Manual fire alarmA-2 load of 164Under 300Not required by 907.2.1907.2.1
15. Area, nonseparated (Type IIB, sprinklered, one story)12,000 / 38,0000.32Passes with no fire barriers508.3.2, Table 506.2
16. Area, separated3,200 / 38,000 + 6,000 / 50,000 + 2,800 / 92,0000.084 + 0.120 + 0.030 = 0.235Passes, but needs 1-hour fire barriers508.4.2, Table 508.4
Occupants by space in a 12,000 sq ft mixed-use exampleBar chart: dining room 160 occupants, retail floor 80, office 19, kitchen 4, stockroom 4; total 267.occupantsDining room, 2,400 sq ft net / 15160Retail sales floor, 4,800 sq ft / 6080.0Office suite, 2,800 sq ft / 15019.0Restaurant kitchen, 800 sq ft / 2004Retail stockroom, 1,200 sq ft / 3004
The dining room supplies 160 of the building’s 267 occupants, which makes the restaurant Group A-2 and sprinklers the whole story. Source: CB&C arithmetic on IBC 2024 Table 1004.5 factors, November 2026.

The restaurant decides the outcome for all three tenants. Section 903.2.1.2 sprinklers every story that contains a qualifying A-2 fire area, so the shop and offices are sprinklered too, and under the nonseparated method the fire area is the whole 12,000 sq ft, far past the 5,000 sq ft A-2 limit. Cutting the dining room to 1,400 sq ft net (94 people, 98 with the kitchen) would not avoid sprinklers unless fire barriers also held the restaurant’s fire area to 5,000 sq ft or less.

The area check in rows 15 and 16 uses the one-story sprinklered (S1) factors in Table 506.2 for Type IIB construction before any frontage increase, which understates what the code allows. Both methods pass, so the nonseparated route saves the cost of 1-hour fire barriers. Per-square-foot prices for the sprinkler line itself are in our fire sprinkler system cost guide.

How does the occupancy group set sprinklers, exits and egress width?

Each group carries its own thresholds in IBC 2024 Chapters 9 and 10. Groups H, I and R are sprinklered at any size, A-2 triggers at 5,000 sq ft or 100 people, and most others at a 12,000 sq ft fire area. A one-exit room may hold 49 occupants in A, B, E, F, M and U, but only 10 in most I and R-1 spaces and 3 in H-1 to H-3.

GroupSprinkler trigger (Section 903.2)Most occupants with one exit (Table 1006.2.1)Exit access travel distance, unsprinklered / sprinklered (Table 1017.2)
A-1, A-3, A-4Fire area over 12,000 sq ft, 300 or more occupants, or off the exit discharge level49200 / 250 ft
A-2Fire area over 5,000 sq ft, 100 or more occupants, or off the exit discharge level49200 / 250 ft
A-5Enclosed accessory areas over 1,000 sq ft49200 / 250 ft
BOnly ambulatory care (4 or more patients who cannot self-evacuate) and lithium battery labs49200 / 300 ft
EFire area over 12,000 sq ft, 300 or more occupants, or off the exit discharge level49200 / 250 ft
F-1Fire area over 12,000 sq ft, more than 3 stories above grade, over 24,000 sq ft combined, or lithium battery manufacturing49200 / 250 ft
F-2No group trigger; general triggers in 903.2.11 still apply49300 / 400 ft
GroupSprinkler trigger (Section 903.2)Most occupants with one exit (Table 1006.2.1)Exit access travel distance, unsprinklered / sprinklered (Table 1017.2)
H-1, H-2, H-3Always3Not permitted / 75, 100, 150 ft
H-4, H-5Always10Not permitted / 175, 200 ft
I-1Always (NFPA 13R allowed in Condition 1)10Not permitted / 250 ft
I-2, I-3Always10Not permitted / 200 ft
I-4Always, unless care is at grade with an exterior door from every care room10150 / 200 ft
MFire area over 12,000 sq ft, more than 3 stories above grade, over 24,000 sq ft combined, or over 5,000 sq ft of upholstered furniture or mattress display49200 / 250 ft
R-1Always10200 / 250 ft
R-2, R-3, R-4Always (NFPA 13D allowed for R-3 and R-4 Condition 1)20200 / 250 ft
S-1Fire area over 12,000 sq ft, more than 3 stories above grade, over 24,000 sq ft combined, or commercial motor vehicle storage over 5,000 sq ft29200 / 250 ft
S-2Enclosed garage over 12,000 sq ft or under another group; open garage over 48,000 sq ft29300 / 400 ft
UNo group trigger49300 / 400 ft

Egress width follows the occupant load, not the group, with one exception. Stairways need 0.3 in per occupant and doors, ramps and corridors 0.2 in; buildings sprinklered throughout with an emergency voice/alarm system may use 0.2 and 0.15 in, except in Groups H and I-2 (IBC 2024 Section 1005.3). Losing any one exit may not cut capacity below 50% of the requirement (Section 1005.5).

Exit count follows the story total: 2 exits for 1 to 500 occupants, 3 for 501 to 1,000 and 4 above 1,000 (Table 1006.3.3). Manual fire alarms also follow the group: Group A at 300 or more assembly occupants, Groups B and M at 500 or more combined, or more than 100 above or below the exit discharge level (IBC 2024 Section 907.2).

What changes when a building changes occupancy?

A change of occupancy, such as office to restaurant or retail to self-storage, falls under Chapter 10 of the 2024 IEBC. The new use needs a certificate of occupancy (Section 1001.3), sprinklers wherever IBC Chapter 9 requires them for the new group (Section 1011.2.1), and full IBC egress or height-and-area compliance when the new group ranks as a higher hazard in Tables 1011.5 and 1011.6.

The IBC defines a change of occupancy as a new classification, or a change in purpose or level of activity, where the code requires a greater degree of safety, accessibility, structural strength, fire protection, egress, ventilation or sanitation (IBC 2024 Chapter 2). The IEBC then ranks groups on two scales, where 1 is the highest hazard (IEBC 2024 Section 1011).

GroupEgress hazard category (Table 1011.5)Height and area hazard category (Table 1011.6)Source
H11IEBC 2024 1011.5, 1011.6
I-2, I-3, I-422IEBC 2024 1011.5, 1011.6
A-1, A-2, A-3, A-432IEBC 2024 1011.5, 1011.6
A-534IEBC 2024 1011.5, 1011.6
I-1; R-1; R-2; R-4 Condition 232IEBC 2024 1011.5, 1011.6
E, M33IEBC 2024 1011.5, 1011.6
F-1, S-143IEBC 2024 1011.5, 1011.6
B; R-3; R-4 Condition 144IEBC 2024 1011.5, 1011.6
F-2, S-2, U54IEBC 2024 1011.5, 1011.6

Run the steps in this order before signing a lease or buying a building for a new use:

  1. Confirm the new group from IBC Chapter 3 and whether the change meets the IBC definition of a change of occupancy.
  2. Compare the old and new groups in IEBC Tables 1011.5 and 1011.6; a lower category number means a higher hazard.
  3. If the new group ranks higher for egress, bring the means of egress to IBC Chapter 10 (IEBC 1011.5.1); if equal or lower, existing egress elements are checked against the IEBC (1011.5.2).
  4. If the new group ranks higher for height and area, check the building against IBC Chapter 5 (IEBC 1011.6.1).
  5. Apply IBC Section 903.2 for the new group; sprinklers go in the changed area and any area not separated from it (IEBC 1011.2.1).
  6. Recalculate occupant load and egress capacity for the new use (IEBC 1011.5.3), and recount plumbing fixtures if the story’s occupant load rises more than 20% (IEBC 1009.1).
  7. Check floor live loads under IBC Section 1607 for the new use (IEBC 1006.1) and kitchen exhaust and ventilation under the International Mechanical Code (IEBC 1008.1).
  8. Permit the work and obtain the new certificate of occupancy (IEBC 1001.3).

Applied to the example building, turning the 2,800 sq ft office suite into a second restaurant gives 2,100 sq ft net of dining (140 people) plus 700 sq ft of kitchen (4 people), 144 occupants and Group A-2. Group B is egress category 4 and A-2 is category 3, so the egress must meet IBC Chapter 10, and the story load rises from 267 to 392, up 46.8%, which forces a plumbing fixture recount under IEBC 1009.1.

The permit and inspection steps that end in the new certificate are covered in our certificate of occupancy guide. Office alterations that keep the same use follow the IEBC alteration levels instead, set out in our office renovation guide.

Which rule applies to your project?

Classify each space in the order the flowchart shows, because the first matching question wins: hazardous materials above the allowable quantity make a space Group H before any other test. The decision table repeats the same logic with the code section behind each answer, then adds the 3 mixed-use and change-of-use calls that most often decide cost.

Flowchart assigning an IBC occupancy group: H, E, I or R, A or B, F, M, S, B, then UClassify each room or area by what happens in it(IBC 2024 Section 302.1). Ask in order:Hazardous materials above the maximumallowable quantity per control area?YesGroup H-1 to H-5Section 307NoGrades K to 12 for 6 or more, or day carefor children older than 2 1/2?YesGroup ESection 305NoPeople sleep there, get care (24-hour orday care), or are detained?YesCare or detention: Group I (308)Sleeping only: Group R (310)NoPeople gather to eat, drink, worship,watch or wait?Yes50 or more occupants: A-1 to A-5 (303)Under 50: Group B (303.1.1)NoGoods made, processed, packagedor repaired?YesF-1, or F-2 if noncombustibleSection 306NoGoods displayed and soldto the public?YesGroup MSection 309NoGoods or vehicles stored?YesS-1, or S-2 if noncombustibleSection 311NoOffices, services, clinics,or education above grade 12?YesGroup BSection 304NoNone of these: Group U (312) for accessory and miscellaneous structures,or the group the use most nearly resembles (302.1)More than one group in the building? Apply Section 508:accessory (10% rule), nonseparated or separated occupancies
Ask the questions in order; the first yes sets the group. Source: ICC, 2024 International Building Code Sections 302 to 312 and 508, accessed November 2, 2026.
IfThenIBC or IEBC 2024 rule
Hazardous materials exceed the maximum allowable quantity per control areaGroup H-1 to H-5; sprinklers always; H-1 in its own buildingIBC 307.1, 903.2.5, Table 508.4
Grades K to 12 for 6 or more, or day care for children older than 2 1/2Group EIBC 305.1, 305.2
People sleep there, get 24-hour or day care, or are detainedCare or detention: Group I; sleeping only: Group R; both sprinklered at any sizeIBC 308, 310, 903.2.6, 903.2.8
People gather to eat, drink, worship, watch or wait, and the occupant load is 50 or moreGroup A-1 to A-5; post the occupant load at the main exitIBC 303, 1004.9
People gather but the occupant load is under 50Group B, or part of the main occupancyIBC 303.1.1, 303.1.2
Goods are made, processed, packaged or repairedF-1, or F-2 if noncombustibleIBC 306
Goods are displayed and sold to the publicGroup MIBC 309
Goods or vehicles are storedS-1, or S-2 if noncombustibleIBC 311
Offices, services, clinics, or education above grade 12Group BIBC 304
None of theseGroup U for accessory and miscellaneous structures, or the group the use most nearly resemblesIBC 312, 302.1
A secondary use takes 10% or less of the storyTreat it as accessory: no separation, main group’s height and areaIBC 508.2
One group is A-2 with 100 or more occupantsSprinkler the whole story; compare nonseparated against the cost of fire barriersIBC 903.2.1.2, 508.3, 508.4
The new use has a lower egress category number than the old oneBring egress up to IBC Chapter 10IEBC 1011.5.1

Which published claims about occupancy groups are wrong?

Several high-ranking explainers repeat separation and sprinkler numbers that do not match the 2024 code text. The corrections below compare claims found on a top-ranking IBC explainer in November 2026 with IBC 2024 Table 508.4 and Sections 303.1.1 and 903.2.1.2, so the reader can check each line against the primary source.

What a top-ranking guide saysWhat the IBC 2024 text saysSource
Group A next to Group B needs 1 hour, or 2 hours if the A occupancy is above the third story1 hour where sprinklered throughout, 2 hours where not; Table 508.4 has no story conditionIBC 2024 Table 508.4
Group H-1 needs a 4-hour separation from any other occupancyH-1 next to any other group is marked NP, not permitted; Section 508.1 exception 2 and Table 415.6.5 can require a detached buildingIBC 2024 Table 508.4, 508.1
A-2 sprinklers apply at an occupant load exceeding 100100 or more: a 100-person fire area triggers sprinklersIBC 2024 903.2.1.2
A 40-seat restaurant is Group BGroup B applies when the occupant load is under 50; loose-seat dining is counted at 15 net sq ft per person, so 800 sq ft net of dining is 53 people and Group A-2 whatever the chair countIBC 2024 303.1.1, Table 1004.5

The occupancy group combines with the construction type in our types of construction guide to set height and area limits, and the exit lighting it triggers is covered in our emergency lighting requirements guide.

How we compiled this

We read 8 primary documents in November 2026: IBC 2024 Chapters 2, 3, 5, 9 and 10 and IEBC 2024 Chapter 10 on ICC Digital Codes, 42 CFR 482.41 on eCFR, and Washington’s amendment WAC 51-50-1004. The worked example is an illustrative building with CB&C arithmetic, not a project we built or inspected. We did not review earlier editions or local amendments other than Washington’s, so confirm both with your building department.

Frequently asked questions

Who decides the occupancy classification of a building?

The architect or engineer proposes the groups in the code summary on the permit drawings, and the building official accepts or changes them. IBC 2024 Section 302.1 tells the official to place any use the code does not list in the group it most nearly resembles by fire safety and relative hazard. The approved group then governs sprinklers, exits and the certificate of occupancy.

Is a college classroom Group B or Group E?

Group B. IBC 2024 Section 304.1 lists educational occupancies for students above the 12th grade, including higher education laboratories, as business uses. Group E under Section 305.1 covers education through the 12th grade for 6 or more people at a time. A college lecture hall holding 50 or more people can still be Group A-3, which names lecture halls.

What is the difference between S-1 and S-2 storage?

S-2 covers noncombustible goods, including products on wood pallets or in paper cartons with only negligible plastic trim, plus parking garages (IBC 2024 Section 311.3). Everything else is S-1, including self-storage, furniture, lumber and tires (Section 311.2). S-1 needs sprinklers above a 12,000 sq ft fire area, while S-2 has a trigger only for parking garages (Sections 903.2.9 and 903.2.10).

Does a restaurant with fewer than 50 seats count as Group A-2?

Not by seat count. IBC 2024 Section 303.1.1 makes an assembly tenant space Group B only when its occupant load is under 50, and Table 1004.5 counts loose-seat dining at 15 net sq ft per person plus 200 gross sq ft per person in the kitchen. A 750 sq ft net dining room alone counts 50 people and is Group A-2.

What occupancy group is a hospital or medical office?

A hospital is Group I-2 under IBC 2024 Section 308.3, because it gives 24-hour medical care to more than 5 people who cannot evacuate unaided. Outpatient clinics and medical offices are Group B, and ambulatory care facilities stay Group B but need sprinklers when 4 or more patients cannot self-evacuate (Section 903.2.2.1). Medicare hospitals also follow the 2012 NFPA 101 Life Safety Code.

What is the occupant load factor for an office?

IBC 2024 Table 1004.5 sets 150 gross sq ft per person for business areas, so a 7,500 sq ft office floor has a design occupant load of 50. Call centers, trading floors and similar dense spaces use the concentrated business rule in Section 1004.8: the actual headcount where the building official approves it, but not less than 1 person per 50 gross sq ft.

Which code edition applies to my building?

The edition your state or city adopted, with its amendments, which may be the 2018, 2021 or 2024 IBC. Ask the building department two questions before design starts: which IBC and IEBC editions it enforces, and whether it amended Chapter 3, Table 1004.5 or Section 903.2. Washington, for example, adds a 50 gross sq ft factor for billiard and game table areas.