Occupant Load Factor: IBC 2024 Table 1004.5, How to Calculate Occupant Load and What It Sets

Empty commercial tenant space with chalk layout lines on a concrete floor and metal stud framing

An occupant load factor is the floor area the code assigns to each person: divide a space’s area by its IBC 2024 Table 1004.5 factor, such as 150 gross sq ft for offices or 15 net for dining.

Key takeaways

  • Offices use 150 gross sq ft per person, retail sales floors 60 gross, commercial kitchens 200 gross and dining at tables and chairs 15 net (IBC 2024 Table 1004.5).
  • Gross area runs to the inside of the exterior walls with no deductions; net area leaves out corridors, stairs, toilet rooms, mechanical rooms and closets (IBC 2024 Chapter 2).
  • A space over 49 occupants in Groups A, B, E, F and M needs 2 exits, and each door needs 0.2 in of width per occupant (IBC 2024 Table 1006.2.1 and Section 1005.3.2).
  • A Group A-2 restaurant with 100 or more occupants needs sprinklers even under 5,000 sq ft (IBC 2024 Section 903.2.1.2).
  • The same number sets restroom counts: the plumbing code halves it by sex and applies ratios such as 1 water closet per 75 for restaurants (IPC 2024 Table 403.1).
  • Business areas moved from 100 to 150 gross sq ft per person in the 2018 IBC, so pre-2018 guides overcount offices by 50% (IBC 2015 Table 1004.1.2).

What is an occupant load factor?

An occupant load factor is the number of square feet of floor area the code assumes for each person in a given use. Section 1004.5 of the 2024 International Building Code (IBC) says the occupant load is not less than the floor area divided by the factor for that function. A lower factor means a denser room: 5 net sq ft for standing space, 500 gross for a warehouse.

The factor is a design assumption for egress, not a comfort standard. The San Francisco Department of Building Inspection quotes the International Code Council (ICC) on this point: 150 gross for business use does not mean each worker gets 150 sq ft, only that the exits are sized for 1 person per 150 sq ft (SF DBI Code Advisory, October 14, 2026). Which group a building falls into is a separate question, covered in our occupancy classification guide.

What are the occupant load factors in IBC Table 1004.5?

IBC 2024 Table 1004.5 lists 41 functions. The ones most commercial projects use are business areas at 150 gross sq ft per person, mercantile at 60 gross, commercial kitchens at 200 gross, storage at 300 gross, and assembly at 5, 7 or 15 net depending on whether people stand, sit in loose chairs or sit at tables. The last column converts each factor to people per 1,000 sq ft.

Function of space (IBC 2024 Table 1004.5)Sq ft per occupantArea basisOccupants per 1,000 sq ft
Standing space (assembly)5Net200
Assembly, chairs only (not fixed)7Net142.9
Gaming floors (keno, slots)11Gross90.9
Assembly, tables and chairs15Net66.7
Stages and platforms15Net66.7
Airport waiting areas15Gross66.7
Pool and rink decks15Gross66.7
Classroom area20Net50
Airport baggage claim20Gross50
Exhibit gallery and museum30Net33.3
Day care35Net28.6
Courtrooms (other than fixed seating)40Net25
Concentrated business use (call centers, trading floors)Actual count, not less than 1 per 50 (Section 1004.8)Gross20 minimum
Exercise rooms50Gross20
Locker rooms50Gross20
Dormitories50Gross20
Library reading rooms50Net20
Shops and vocational rooms50Net20
Rink and pool (water and ice surface)50Gross20
Mercantile (sales floor)60Gross16.7
Industrial areas100Gross10
Outpatient areas100Gross10
Library stack area100Gross10
Airport concourse100Gross10
Institutional sleeping areas120Gross8.3
Business areas (offices)150Gross6.7
Kitchens, commercial200Gross5
Residential200Gross5
Parking garages200Gross5
Group H-5 fabrication and manufacturing200Gross5
Inpatient treatment areas240Gross4.2
Storage, stock and shipping areas300Gross3.3
Accessory storage, mechanical equipment room300Gross3.3
Information technology equipment facilities (new in 2024)300Gross3.3
Agricultural building300Gross3.3
Airport baggage handling300Gross3.3
Warehouses500Gross2
Aircraft hangars500Gross2
Fixed seats, benches, boothsSeat count; 18 in of bench or 24 in of booth per person (Section 1004.6)Countn/a
Bowling centers5 per lane incl. 15 ft of runway, plus 7 net for other areasNetn/a
Mall buildingsSee Section 402.8.2Grossn/a
Occupants per 1,000 sq ft by IBC functionBar chart: standing space holds 200 people per 1,000 sq ft, dining 66.7, retail 16.7, offices 6.7, warehouses 2occupants per 1,000 sq ftStanding space (5 net)200Chairs only (7 net)143Gaming floors (11 gross)90.9Tables and chairs (15 net)66.7Classroom (20 net)50.0Exercise rooms (50 gross)20.0Mercantile (60 gross)16.7Industrial (100 gross)10.0Business (150 gross)6.7Commercial kitchens (200 gross)5Storage, stock, shipping (300 gross)3.3Warehouses (500 gross)2
Standing space counts 100 times as many people per 1,000 sq ft as a warehouse: 200 versus 2 (IBC 2024 Table 1004.5, ICC, accessed November 2026).

Where a use is not listed, Section 1004.5 tells the building official to apply the listed function that most nearly resembles it. A coworking lounge, for example, may be argued as business (150 gross) or as unconcentrated assembly (15 net), and the answer changes the count by a factor of 10, so settle it at a pre-application meeting rather than at plan review.

Should you measure gross or net floor area?

Use whichever basis the factor names. Gross floor area is measured to the inside of the exterior walls and keeps corridors, stairs, closets, columns and interior wall thickness; net floor area is the occupied area only and drops corridors, stairways, ramps, toilet rooms, mechanical rooms and closets (IBC 2024 Section 202).

Item in the spaceCounted in gross areaCounted in net areaSource
Interior walls and columnsYesNoIBC 2024 Section 202
Corridors, stairways, rampsYesNoIBC 2024 Section 202
Toilet roomsYesNoIBC 2024 Section 202
Mechanical rooms and closetsYesNoIBC 2024 Section 202
Vent shafts and courtsNoNoIBC 2024 Section 202
Fixed equipment, built-in cabinetsYesNo (deducted in practice)SF DBI Code Advisory, Oct 2026; NFPA fact sheet

In a mixed space, Section 1004.3 has each function calculated on its own area. The practical method is to subtract the net assembly rooms from the suite, then apply the gross factor to what is left. The SF DBI advisory says the same: show gross business area and net assembly areas separately on the code plan.

How do you calculate occupant load step by step?

Measure each function’s area on the basis its factor names, divide by the Table 1004.5 factor, round each space up to a whole person, then add the spaces that share an egress path. The total sets exits, egress width, door hardware, sprinkler triggers, plumbing fixtures and the posted sign.

  1. Split the floor plan by function: office, conference, dining, kitchen, sales, stock. Rooms used for 2 purposes are calculated for each use (IBC 2024 Section 1004.3).
  2. Measure gross area for gross factors and net area for net factors, in sq ft, from the dimensioned plan.
  3. Count fixed seating instead of area: 1 per seat, 1 per 18 in of bench and 1 per 24 in of booth measured at the backrest (Section 1004.6).
  4. Divide each area by its factor and round each space up. The IBC text sets no rounding rule; the SF DBI advisory of October 2026 and the NFPA fact sheet both round each room up.
  5. Add the spaces that egress through one another or share a path (Section 1004.2). Stories are not added together except where stairs converge (Section 1004.2.3).
  6. Add outdoor patios or roof decks whose occupants egress through the building, at a load the building official assigns (Section 1004.7).
  7. Carry the total into Sections 1005, 1006 and 1010 for width, exits and doors, and into IPC Table 403.1 for fixtures.
Flow diagram: 4 calculation steps lead to the occupant load, which sets exits, width, doors, sprinklers, fixtures, signsHow the occupant load is calculated and what it sets (IBC 2024, IPC 2024)1. Measure each spacegross or net, per its factor2. Pick the Table 1004.5 factorby function, not by tenant3. Divide and round upeach function apart (1004.3)4. Add spaces on one pathcumulative load (1004.2)Design occupant loadExitsover 49 in a space: 2 (1006.2.1)story 501+: 3; 1,001+: 4Egress widthdoors 0.2 in each (1005.3.2)stairs 0.3 in each (1005.3.1)Doors50+: swing out (1010.1.2.1)A or E 50+: panic hardwareSprinklersA-2 at 100+ (903.2.1.2)A-1, A-3 at 300+Plumbing fixturesIPC Table 403.1 ratioshalf per sex, round upPostingevery assembly roomnear main exit (1004.9)
Four steps produce the design occupant load, which then sets 6 code outputs (IBC 2024 Sections 1004 to 1010 and 903, IPC 2024 Table 403.1, accessed November 2026).

Two adjustments run the other way. An owner may design for more people than the table gives, up to 1 occupant per 7 sq ft, if exits and fixtures are sized for the higher number (Section 1004.5.1). The building official may also approve a lower actual headcount (Section 1004.5 exception), which is how a lightly staffed lab or archive avoids oversizing. Both changes end up on the certificate of occupancy as the approved load.

How many occupants does a 6,000 sq ft office hold?

A 6,000 gross sq ft office suite with a 480 sq ft conference room and 300 sq ft of storage has an occupant load of 68, not the 40 that 6,000 / 150 suggests. The conference room is counted at 15 net sq ft per person, which adds 28 people and pushes the suite past 49, the one-exit limit.

StepInputArithmeticResultRule
Conference room, tables and chairs24 ft x 20 ft = 480 sq ft net480 / 1532Table 1004.5
Storage and file room300 sq ft gross300 / 3001Table 1004.5
Business area (rest of suite)6,000 – 480 – 300 = 5,220 sq ft gross5,220 / 150 = 34.835Table 1004.5, 1004.3
Suite occupant load32 + 1 + 35Sum681004.2
Single-factor shortcut (for comparison)6,000 sq ft gross6,000 / 15040Undercounts by 28
Exits from the suite68 occupants, Group BOver 492Table 1006.2.1
Exits from the conference room32 occupants49 or fewer1 (stays Group B)Table 1006.2.1, 303.1.2
Door capacity68 x 0.2 in13.6 in32 in clear door governs1005.3.2, 1010.1.1
Corridor width68 occupants50 or more44 in (36 in under 50)Table 1020.3
Door swing68 occupants50 or moreSuite exit doors swing out1010.1.2.1
Office suite plan comparing a 40-person single-factor count with the 68-person count by functionExample 1: 6,000 sq ft office suite (100 ft x 60 ft), counted by functionConference24 x 20 = 480 net480 / 15 = 32Storage300 gross300 / 300 = 1Business area (open office, private offices, restrooms, corridor)6,000 – 480 – 300 = 5,220 sq ft gross5,220 / 150 = 34.8, round up: 35Exit 1Exit 2100 ftShortcut: 6,000 / 150 = 401 exit could look allowed (49 or fewer)By function: 32 + 1 + 35 = 682 exits (Table 1006.2.1), doors swing out
Counting the 480 sq ft conference room at 15 net raises a 6,000 sq ft office from 40 to 68 occupants and to 2 required exits (IBC 2024 Table 1004.5 and Table 1006.2.1). Illustrative CB&C plan.

The fixture count uses the same 68. IPC 2024 Section 403.1.1 splits the load in half, 34 per sex, and rounds every fraction up. The business row of Table 403.1 calls for 1 water closet per 25 for the first 50, so 34 / 25 = 1.36 becomes 2 per sex, plus 1 lavatory per sex, 1 drinking fountain and 1 service sink. Designing all-gender multi-user rooms instead counts 100% of the 68: 3 water closets and 2 lavatories.

Fixture (IPC 2024 Table 403.1, business)RatioSeparate rooms (34 per sex)All-gender rooms (68 total)
Water closets1 per 25 for the first 50, then 1 per 502 + 2 = 450/25 + 18/50 = 2.36, so 3
Lavatories1 per 40 for the first 80, then 1 per 801 + 1 = 268/40 = 1.7, so 2
Drinking fountain1 per 1001 (a dual-spout unit meets IPC 410.3.1)1
Service sink1 (not required at 15 or fewer)11

Separate men’s and women’s rooms are required here because a business occupancy over 25 people loses the single-facility exception in IPC 2024 Section 403.2. Budget numbers for the fit-out itself are in our office renovation guide.

What is the occupant load of a 3,200 sq ft restaurant?

An 80 ft by 40 ft restaurant with 1,360 sq ft of dining tables, 40 ft of booths, a standing waiting area, a 900 sq ft kitchen and storage has an occupant load of 133. That makes it Group A-2, and because 133 is 100 or more, IBC 2024 Section 903.2.1.2 requires sprinklers even though the fire area is under 5,000 sq ft.

Dimensioned 80 by 40 ft restaurant plan with each room's area, factor and occupant count totalling 133Example 2: 3,200 sq ft restaurant (80 ft x 40 ft), IBC 2024 Table 1004.5Restrooms320 sq ftnot countedWaiting80 net / 5= 16Booths: 40 ft of seat = 480 in / 24 = 20Dining, tables and chairs40 ft x 34 ft = 1,360 sq ft net1,360 / 15 = 90.7, round up: 91Commercial kitchen30 ft x 30 ft = 900 sq ft gross900 / 200 = 4.5, round up: 5Corridor100 sq ftStorage 200 gross200 / 300 = 0.7: 180 ft40 ftExit 1 (main entry)Exit 232 ft apart (1/3 of the 89.4 ft diagonal is 29.8 ft, sprinklered)Total: 91 + 20 + 16 + 5 + 1 = 133 occupants, Group A-22 exits (Table 1006.2.1) | door capacity 133 x 0.2 in = 26.6 in (1005.3.2) | panic hardware (1010.2.8)Sprinklers: 100 or more A-2 occupants (903.2.1.2) | post 133 near the main exit (1004.9)
An 80 ft by 40 ft restaurant counts 133 occupants under IBC 2024 Table 1004.5, enough to require 2 exits and sprinklers (Sections 1006.2.1 and 903.2.1.2). Illustrative CB&C plan.
SpaceSizeFactorArithmeticOccupants
Dining, tables and chairs40 ft x 34 ft = 1,360 sq ft net15 net1,360 / 15 = 90.791
Booths along the wall40 ft of seat at the backrest24 in per person480 in / 2420
Waiting area, standing10 ft x 8 ft = 80 sq ft net5 net80 / 516
Commercial kitchen30 ft x 30 ft = 900 sq ft gross200 gross900 / 200 = 4.55
Storage20 ft x 10 ft = 200 sq ft gross300 gross200 / 300 = 0.71
Restrooms and back corridor420 sq ftNot occupied (net basis)n/a0
Total3,200 sq ft91 + 20 + 16 + 5 + 1133
What the 133 setsRequirementIBC 2024 or IPC 2024 rule
Occupancy groupA-2 (assembly with 50 or more)IBC 303.1.1, 303.3
Exits2 from the dining room and the tenant spaceIBC Table 1006.2.1
Exit separation1/3 of the 89.4 ft diagonal = 29.8 ft when sprinklered (1/2 = 44.7 ft if not); the plan’s doors are 32 ft apartIBC 1007.1.1
Second exit pathNot through the kitchen or storage roomIBC 1016.2 item 6
Door capacity133 x 0.2 in = 26.6 in; two 32 in doorsIBC 1005.3.2, 1005.5
Door hardwarePanic or fire exit hardware on latched exit doors; doors swing outIBC 1010.2.8, 1010.1.2.1
SprinklersRequired: 133 is 100 or moreIBC 903.2.1.2
Manual fire alarmNot required by group (under 300)IBC 907.2.1
Posted sign133 near the main exit, for each layoutIBC 1004.9
Water closets66.5 per sex / 75 = 0.89, so 1 eachIPC Table 403.1
Lavatories66.5 / 200, so 1 eachIPC Table 403.1
Drinking fountainNot required if free water is served in a containerIPC 410.4
Service sink1IPC Table 403.1

The factor choice moves the sprinkler line. With the booths, waiting area, kitchen and storage fixed at 42 people, the dining room would have to shrink to 855 sq ft net (57 people) to keep the total at 99. Set the same 1,360 sq ft with chairs only for events and it counts at 7 net: 195 in the dining room alone, which Section 1004.9 expects on the posted sign for that configuration. Seasonal patio seating also counts toward restroom fixtures under footnote d of IPC Table 403.1.

Owners planning a fit-out can compare kitchen layouts in our commercial kitchen design guide and the sprinkler line item in our fire sprinkler system cost guide, or find restaurant build-out contractors.

How many occupants does a 10,000 sq ft retail store hold?

A 10,000 gross sq ft store with an 8,200 sq ft sales floor, a 1,500 sq ft stockroom and a 300 sq ft office has an occupant load of 144. Running the whole building at the 60 gross mercantile factor gives 167, so splitting out the stockroom at 300 gross removes 23 people from the exit and fixture math.

StepInputArithmeticResultRule
Sales floor (includes restrooms and vestibule)8,200 sq ft gross8,200 / 60 = 136.7137Table 1004.5
Stockroom1,500 sq ft gross1,500 / 3005Table 1004.5
Manager’s office300 sq ft gross300 / 1502Table 1004.5
Store occupant load137 + 5 + 2Sum1441004.2
Single-factor shortcut10,000 sq ft gross10,000 / 60 = 166.7167Overcounts by 23
Exits144, Group MOver 492Table 1006.2.1
Door capacity144 x 0.2 in28.8 in32 in clear door governs1005.3.2, 1010.1.1
Sprinklers by sizeFire area 10,000 sq ftNot over 12,000Not triggered by Group M size903.2.7
Manual fire alarm144Under 500Not required by Group M907.2.7
Posted signGroup MNot assemblyNot required by 1004.91004.9
Separate restrooms144Over 100 in mercantileRequired (or all-gender rooms)IPC 403.2
Water closets / lavatories72 per sex72/500 and 72/7501 + 1 eachIPC Table 403.1
Drinking fountains144 / 1,000Round up1 (high and low, or dual-spout)IPC Table 403.1, 410.3.1

The 100-person mercantile line in IPC 2024 Section 403.2 is worth checking early: a store of 6,000 gross sq ft or less on one sales floor counts at most 100 at 60 gross and may use a single toilet room. More retail planning detail is in our retail construction guide.

What does the occupant load number set?

The design occupant load drives six outputs: exit count, egress width, door swing and hardware, sprinkler and alarm triggers, plumbing fixtures and the posted sign. Each one has a fixed threshold in the code, so a count of 49 versus 50, or 99 versus 100, can add a door, panic hardware or a sprinkler system.

Threshold ladder showing what changes at 15, 26, 50, 100, 300 and 501 occupantsWhat changes as the occupant load grows (IBC 2024 and IPC 2024)15 or fewerone toilet room OK; no service sink (B, M);no drinking fountain (IPC 403.2, 410.2)26+ B, 101+ Mseparate facilities per sex in business (26+)and mercantile (101+), or all-gender rooms (IPC 403.2)50+ in a space2 exits over 49; doors swing out;A becomes assembly; A, E panic hardware100+ in A-2sprinklers required(IBC 903.2.1.2)300+ in Amanual fire alarm (907.2.1);A-1, A-3 sprinklers501+ per story3 exits (Table 1006.3.3);1,001+: 4 exits
Thresholds at 15, 26, 50, 100, 300 and 501 occupants add restrooms, exits, panic hardware, sprinklers and alarms (IBC 2024 and IPC 2024, accessed November 2026).
Occupant loadWhat changesSource
15 or fewerSeparate restrooms, service sink (B, M) and drinking fountain not requiredIPC 2024 403.2, Table 403.1 note e, 410.2
26 or more in businessSeparate facilities per sex, or all-gender roomsIPC 2024 403.2
50 or more in a space2 exits (over 49 in A, B, E, F, M); doors swing out; an assembly room becomes Group A; A and E doors get panic hardwareIBC 2024 Table 1006.2.1, 1010.1.2.1, 303.1.2, 1010.2.8
50 or more on a corridorCorridor 44 in instead of 36 inIBC 2024 Table 1020.3
100 or more in A-2Sprinklers throughout the storyIBC 2024 903.2.1.2
101 or more in mercantileSeparate facilities per sex, or all-gender roomsIPC 2024 403.2
300 or more in AManual fire alarm; A-1 and A-3 sprinklersIBC 2024 907.2.1, 903.2.1
501 to 1,000 per story or space3 exitsIBC 2024 Table 1006.3.3, 1006.2.1.1
Over 1,0004 exitsIBC 2024 Table 1006.3.3, 1006.2.1.1
Any countDoors 0.2 in per occupant, stairs 0.3 in (0.15 and 0.2 with sprinklers and voice alarm, not H or I-2)IBC 2024 1005.3

Stair width follows the same count: 0.3 in per occupant served, with a 44 in minimum (IBC 2024 Section 1011.2), which our stair riser height guide works through for multistory floors. Rooms that need 2 exits also need emergency egress lighting, covered in our emergency lighting requirements guide.

Which factor and rule applies to your space?

Match the room’s furniture and use to the factor first, then check the threshold it lands on. The table below covers the questions that come up most on office, restaurant and retail tenant improvements under the 2024 IBC and IPC.

IfThenSource
Conference or training room with tables15 net sq ft per person; under 50 people it stays part of the business occupancyIBC 2024 Table 1004.5, 303.1.2
Same room set with chairs only7 net sq ft per person; post the load for each layoutIBC 2024 Table 1004.5, 1004.9
Huddle, phone and focus rooms used by office staffCount as business area at 150 grossSF DBI Code Advisory, Oct 2026
Call center, trading floor, dense data entryActual count, not less than 1 per 50 gross sq ftIBC 2024 1004.8
Bar or lobby where people stand5 net sq ft per personIBC 2024 Table 1004.5
Booths or benches24 in of booth or 18 in of bench per personIBC 2024 1004.6
You want more people than the table allowsUp to 1 per 7 sq ft, with exits and fixtures sized to match and a seating diagram if askedIBC 2024 1004.5.1
You will never have the calculated numberAsk the building official to approve the actual countIBC 2024 1004.5 exception
Restaurant count lands between 95 and 105Re-check dining layout: 100 triggers sprinklers in A-2IBC 2024 903.2.1.2
Office count lands at 24 to 26, or store at 98 to 102Check whether one restroom is still allowedIPC 2024 403.2

Some fire marshals enforce NFPA 101, the Life Safety Code, alongside the IBC. Its Table 7.3.1.2 matches the IBC on business (150) and tables-and-chairs assembly (15 net) but adds a 30 sq ft per person factor for collaboration rooms of 450 sq ft or less, a row the IBC does not have (NFPA fact sheet, Calculating Occupant Load). Ask the reviewer which code governs before the furniture plan is final.

Which published occupant load figures are out of date?

Most errors on page-one guides come from older code editions. Business areas changed from 100 to 150 gross sq ft per person and the table moved from 1004.1.2 to 1004.5 in the 2018 IBC, and the 2024 edition added a 300 gross row for information technology equipment facilities.

What some guides sayWhat the primary source saysSource
A guide updated in 2014 cites “Table 1004.1.2” for occupant load factorsTable 1004.1.2 is the 2015 and earlier number; 2018, 2021 and 2024 use Table 1004.5IBC 2015, IBC 2018
Offices: 100 gross sq ft per person150 gross since the 2018 IBC; 100 gross was the 2015 valueIBC 2018 Table 1004.5, IBC 2021
A glossary page uses 10 m2 (about 108 sq ft) per office worker with no source150 gross sq ft (about 13.9 m2) per personIBC 2024 Table 1004.5
Small meeting rooms at 30 sq ft per personNFPA 101 only; the IBC treats staff huddle rooms as business areaNFPA fact sheet; SF DBI Code Advisory
Every room must post its occupancy limitIBC 1004.9 requires the posted load in assembly rooms and spacesIBC 2024 1004.9
Server rooms count at the business factorInformation technology equipment facilities have their own 300 gross factor in 2024IBC 2024 Table 1004.5

Your jurisdiction may still enforce the 2018 or 2021 IBC, or a state amendment, so check the adopted edition on the permit set. This page reads the model codes and is not legal or design advice; the architect of record and the building official decide the final occupant load.

The occupant load also drives door and lift choices, covered in our commercial door sizes and commercial elevator cost guides.

How we compiled this

We read IBC 2024 Chapters 2, 3, 9 and 10 and IPC 2024 Chapter 4 on ICC Digital Codes, plus the 2015, 2018 and 2021 IBC Chapter 10 to date each factor change, 7 primary documents in all, between November 2 and November 9, 2026. We added the SF DBI Code Advisory of October 14, 2026 and the NFPA occupant load fact sheet for practice notes. The 3 worked examples are illustrative CB&C spaces, not real projects, and every number in them is arithmetic from the cited tables.

Frequently asked questions

What is the occupant load factor for an office?

Business areas use 150 gross sq ft per person under IBC 2024 Table 1004.5, so a 4,500 sq ft office counts 30 people. Conference rooms inside the office count separately at 15 net with tables or 7 net with chairs only. Call centers and trading floors use the actual count, but not less than 1 person per 50 gross sq ft (Section 1004.8).

What is the occupant load factor for a restaurant?

Dining at tables and chairs uses 15 net sq ft per person, standing areas 5 net, booths 1 person per 24 in of seat, and the commercial kitchen 200 gross (IBC 2024 Table 1004.5 and Section 1004.6). A restaurant that reaches 50 becomes Group A-2, and one that reaches 100 needs sprinklers under Section 903.2.1.2.

Do you round occupant load up or down?

Round each space up to the next whole person. The IBC text sets no rounding rule, but the SF DBI Code Advisory of October 2026 and the NFPA fact sheet both round each room up, and IPC 2024 Section 403.1.1 rounds every fixture fraction up. A 5,220 sq ft office area at 150 gross gives 34.8, counted as 35.

Is occupant load the same as maximum capacity?

The calculated occupant load is the minimum number of people the exits must be designed for, not a cap. Section 1004.5.1 lets an owner raise it to 1 person per 7 sq ft if exits and fixtures are sized to match. The posted sign in an assembly room (Section 1004.9) then becomes the enforced limit for that layout.

How many exits does an occupant load of 50 require?

In Groups A, B, E, F, M and U, a space with more than 49 occupants needs 2 exits or exit access doorways under IBC 2024 Table 1006.2.1, and its doors must swing in the direction of egress (Section 1010.1.2.1). Stories need 2 exits up to 500 people, 3 from 501 to 1,000 and 4 above 1,000 (Table 1006.3.3).

How does occupant load set the number of toilets?

IPC 2024 Section 403.1 takes the occupant load from the IBC, splits it in half by sex, and applies Table 403.1 ratios: 1 water closet per 75 for restaurants, 1 per 25 for the first 50 in offices, 1 per 500 in retail. Fractions round up, and single-sex rooms are not required at 15 or fewer people.

Sources